Wall |
WM1
|
Masonry / Concrete |
-/120/- |
IFD44CASED |
Mounted in casing |
2400 x 2400 |
|
|
WM3
|
Masonry / Concrete |
-/120/- |
IFD44 |
Cell only |
2400 x 2400 or 5.76 m2 |
|
|
WM3i
|
Masonry / Concrete |
-/120/120 |
IFD44 |
Cell only - Transfer Air with mesh guard |
2400 x 1200 |
|
|
WM4
|
Masonry / Concrete |
-/120/- |
IFD44 |
Cell only - Surface mounted (max peno size 500 x 500) |
600 x 600 |
|
|
WM5
|
Masonry / Concrete |
-/120/120 |
IFD44-LL |
Duct to duct / duct to gri |
350 DIA |
|
|
WM6
|
Masonry / Concrete |
-/240/- |
IFD-O |
Spiral duct sleeve grouted into penetration (angle free) |
150 DIA |
|
|
WM7
|
Masonry / Concrete |
-/120/- |
IFD-OSS |
Stainless steel casing |
350 DIA |
|
|
WM8
|
Masonry / Concrete |
-/120/- |
IFD-O |
Spiral duct sleeve grouted into penetration (angle free) |
300 DIA |
|
|
WM10
|
Masonry / Concrete |
-120/- |
IFD-O |
IFD-O Hi-Flow |
200 DIA |
|
|
WM11
|
Masonry / Concrete |
-/120/- |
IFD44 |
Cell only - various fixing brackets |
10m x 600mm |
|
|
WH1
|
Hebel |
-120/- |
IFD44CASED |
Mounted in casing in 75SS system hebel wall |
2400 x 2400 |
|
|
WH3
|
Hebel |
-120/- |
IFD44CASED |
Mounted in casing in 75SW system hebel wall |
2400 x 2400 |
|
|
WH5
|
Hebel |
-120/- |
IFD44CASED |
Mounted in casing tight to underside of slab connected to riser but with angles on 3 sides of the IFD on 1 side of the wall |
300 x 300 |
|
|
WH6
|
Hebel |
-120/- |
IFD-O |
Mounted in casing tight to underside of slab |
150 DIA |
|
|
WH7
|
Hebel |
-120/- |
IFD44CASED |
Mounted in casing tight to underside of slab with angles on 3 side of the IFD on 1 side of the wall |
300 x 300 |
|
|
WH8
|
Hebel |
-120/- |
IFD44 |
Mounted in casing connected to riser, angle free system |
600 x 600 or 0.36 m2 |
|
|
WS1
|
CSR Security Wall |
-/90/90 |
IFD44CASED |
Mounted in casing |
600 x 600 |
with cover grille |
|
WS2
|
CSR Security Wall |
-/90/- |
IFD-O |
DD / DG |
300 DIA |
|
|
WP1
|
FR Plasterboard 1 x 16 |
-/90/- |
IFD44CASED |
Mounted in casing with angles both sides |
2400 x 2400 |
|
|
WP2
|
FR Plasterboard 3 x 16 |
-/120/- |
IFD44CASED |
Mounted in casing with angles both sides |
2400 x 2400 or 5.76 m2 |
|
|
WP7
|
FR Plasterboard 2 x 16 |
-/120/- |
IFD44 |
Cell only with various fixing methods |
2400 x 2400 or 5.76 m2 |
|
|
WP8
|
FR Plasterboard 1 x 13 |
-/60/- |
IFD44CASED |
Mounted in casing angles both sides |
2400 x 2400 |
|
|
WP9
|
FR Plasterboard 2 x 13 |
-/90/- |
IFD44CASED |
Mounted in casing angles both sides |
2400 x 2400 |
|
|
WP10
|
FR Plasterboard 1 x 13 |
-/60/- |
IFD44 |
Cell only with various fixing methods |
2400 x 2400 or 5.76 m2 |
|
|
WP11
|
FR Plasterboard 2 x 13 |
-/90/- |
IFD44 |
Cell only with various fixing methods |
2400 x 2400 or 5.76 m2 |
|
|
WSP1
|
Speedpanel |
-/120/- |
IFD44CASED |
Mounted in casing under slab with fire rated board in top track |
1000 x 1000 |
|
|
WSP2
|
Speedpanel |
-/120/- |
IFD44CASED |
Mounted in casing above slab with fire rated board in bottom track |
1000 x 1000 |
|
|
WSP3
|
Speedpanel |
-/120/- |
IFD44CASED |
Mounted in casing |
1000 x 1000 |
|
|
WSP4
|
Speedpanel |
-/120/- |
IFD44CASED |
Mounted in casing with 2 x layers of 13mm plasterboard |
1000 x 1000 |
|
|
WSP5
|
Speedpanel |
-/120/- |
IFD-O |
Mounted in casing DD / DG |
300 DIA |
|
|
WV1
|
Vermiculux Board |
-/120/- |
IFD44 |
Cell only - Surface mounted (max peno size 500 x 500) |
600 x 600 |
|
|
WV2
|
Vermiculux Board |
-/120/- |
IFD44 |
Cell only - mounted within wall |
800 x 800 |
|
|
WV3
|
Vermiculux Board + 2 x PB |
-/120/- |
IFD44 |
Cell only - mounted within wall with 2 layers of plasterboard lining |
800 x 800 |
|
|
WM5i
|
Masonry / Concrete |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
Shaftwall Duct |
WSRF1
|
Masonry / Plasterboard 3 x 16 |
-/120/- |
IFD44 |
Retrofit cell only in ductwork branch in masonry / 3 x 16mm plasterboard shaftwall |
600 x 600 or 0.36 m2 |
|
|
WSW1
|
Masonry / Hebel |
-/120/- |
IFD44CASED |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW2
|
Masonry / Hebel |
-/120/- |
IFD44CASED |
Mounted in casing - angle free riser connection tight to slab with packer |
600 x 600 or 0.36 m2 |
|
|
WSW3
|
Masonry |
-/120/- |
IFD-O |
Mounted in casing - angle free riser connection |
300 DIA |
|
|
WSW4
|
Plasterboard 3 x 16 |
-/120/- |
IFD44CASED |
Mounted in casing - angle free riser connection tight to slab with packer |
600 x 600 or 0.36 m2 |
|
|
WSW5
|
Plasterboard 3 x 16 |
-/120/- |
IFD44CASED |
Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic |
600 x 600 or 0.36 m2 |
|
|
WSW6
|
Plasterboard 3 x 16 |
-/120/- |
IFD-O |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW7
|
Plasterboard 3 x 16 |
-/120/- |
IFD44CASED |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW8
|
Plasterboard 2 x 16 |
-/120/- |
IFD44CASED |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW9
|
Plasterboard 2 x 16 |
-/120/- |
IFD-O |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW10
|
Plasterboard 1 x 13 |
-/60/- |
IFD44CASED |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW11
|
Plasterboard 2 x 13 |
-/90/- |
IFD44CASED |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW12
|
Plasterboard 1 x 16 |
-/60/- |
IFD44CASED |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
Floor/Slab |
FL1
|
Concrete Slab |
-/120/- |
IFD44 |
No casing in penetration |
2400 x 2400 or 5.76 m2 |
|
|
FL2
|
Concrete slab |
-/240/180 |
IFD44 |
Mounted in casing |
300 x 300 |
|
|
FL3
|
Concrete slab |
-/120/120 |
IFD44 |
Mounted in casing |
600 x 600 or 0.36 m2 |
|
|
FL5
|
Concrete slab |
-/120/- |
IFD44 |
Cell only - surface mounted over or under penetration |
600 x 600 |
|
|
FL6
|
Concrete slab |
-/120/120 |
IFD-O |
NO steel sleeve in penetration |
250 DIA |
|
|
FL7
|
Concrete slab |
-/120/- |
IFD44 |
Mounted in steel casing in penetration |
2400 x 2400 or 5.76 m2 |
|
|
FLV1
|
Vermiculux OR Promatect Board |
-/120/120 |
IFD44 |
NO casing in penetration |
800 x 800 |
|
|
FLV2
|
Vermiculux OR Promatect Board |
-/120/120 |
IFD44 |
NO casing - surface mounted over penetration |
800 x 800 |
|
|
FLV3
|
Vermiculux OR Promatect Board |
-/120/120 |
IFD44 |
NO casing - surface mounted under penetration |
800 x 800 |
|
Ceiling |
CE1
|
FR P/Board 2 ply ceiling |
-/60/60 |
IFD-CE1 |
P/Board clad encl. (60 min RISF Incipient rated) |
600 x 600 |
|
|
CE2
|
FR P/Board 2 ply ceiling |
-/60/60 |
IFD-CE2 |
P/Board clad encl. open end (60 min RISF Incipient rated) |
300 x 300 |
|
|
CE3
|
FR P/Board 2 ply ceiling |
-/90/90 |
IFD-CE3 |
P/Board panel & IFD (90 min RISF Incipient rated) |
150mm diameter |
|
|
CE4
|
FR P/Board 2 ply ceiling |
-/90/90 |
IFD-CE4 |
P/Board clad 3 way enclosure (90 min RISF Incipient rated) |
440 x 440 |
|