Application:
This sealing combination is suitable for typical isolation room applications where quantifiable ambient temperature air/smoke leakage rates are required to be tested in accordance with AS1530 Part 7, as per engineered specifications.
Approvals:
This system is tested in accordance with BS476:Part 31 (Methods for measuring smoke penetration through doorsets and shutter assemblies) Section 31.1:1983 (Method of measurement under ambient temperature conditions).
Proof:
Ambient Temperature Test Results
Door Configuration / Pressure | Exposure Temp | Door Perimeter Tested | Leakage Rate (m3h) @ a Pressure Differential of | ||
---|---|---|---|---|---|
10Pa | 25Pa | 50Pa | |||
Opening Towards Positive Pressure (Inswing) | Ambient (nom. 20ÂșC) | Entire Perimeter | 1.6 | 3.1 | 4.8 |
Note: The ambient test consisted of a single-acting, single-leaf proprietary doorset, fitted with the specified smoke seals, utilising the general principles of BS476:Part 31 (Methods for measuring smoke penetration through doorsets and shutter assemblies) Section 31.1:1983 (Method of measurement under ambient temperature conditions).
For more information and copies of relevant certificates contact Kilargo