IS7025si, IS8010si (fire & smoke)

Application:

This sealing combination is suitable for typical isolation room applications where quantifiable ambient temperature air/smoke leakage rates are required to be tested in accordance with AS1530 Part 7, as per engineered specifications.

Approvals:

This system is tested in accordance with BS476:Part 31 (Methods for measuring smoke penetration through doorsets and shutter assemblies) Section 31.1:1983 (Method of measurement under ambient temperature conditions).

Proof:

Ambient Temperature Test Results

Door Configuration / Pressure Exposure Temp Door Perimeter Tested Leakage Rate (m3h) @ a Pressure Differential of
10Pa 25Pa 50Pa
Opening Towards Positive Pressure (Inswing) Ambient (nom. 20ÂșC) Entire Perimeter 1.6 3.1 4.8

Note: The ambient test consisted of a single-acting, single-leaf proprietary doorset, fitted with the specified smoke seals, utilising the general principles of BS476:Part 31 (Methods for measuring smoke penetration through doorsets and shutter assemblies) Section 31.1:1983 (Method of measurement under ambient temperature conditions).

For more information and copies of relevant certificates contact Kilargo

Product Fact Sheets: