IS1212, IS8010si (fire)

Application:

This sealing combination, fitted to a nominal 35mm solid core door construction, is suitable for typical isolation room applications where quantifiable ambient temperature air/smoke leakage rates are required to be tested in accordance with AS1530 Part 7, as per engineered specifications.

Approvals:

This system is tested in accordance with AS1530 Part 7 (Method of measurement under ambient temperature conditions).

Proof:

Ambient Temperature Test Results

Door Configuration / Pressure Exposure Temp Door Perimeter Tested Leakage Rate (m3h) @ a Pressure Differential of
10Pa 25Pa 50Pa
Inswing Ambient (nom. 25ºC) Entire Perimeter 10 16 18
Outswing Ambient (nom. 25ºC) Entire Perimeter 4 6 9

Note: The ambient test consisted of a single-acting, single-leaf proprietary doorset, fitted with the specified smoke seals, utilising the general principles of AS1530 Part 7 – 1998 (Method of measurement under ambient temperature conditions).

For more information and copies of relevant certificates contact Kilargo