Application:
This sealing combination, fitted to a nominal 35mm solid core door construction, is suitable for typical isolation room applications where quantifiable ambient temperature air/smoke leakage rates are required to be tested in accordance with AS1530 Part 7, as per engineered specifications.
Approvals:
This system is tested in accordance with AS1530 Part 7 (Method of measurement under ambient temperature conditions).
Proof:
Ambient Temperature Test Results
Door Configuration / Pressure | Exposure Temp | Door Perimeter Tested | Leakage Rate (m3h) @ a Pressure Differential of | ||
---|---|---|---|---|---|
10Pa | 25Pa | 50Pa | |||
Inswing | Ambient (nom. 25ºC) | Entire Perimeter | 10 | 16 | 18 |
Outswing | Ambient (nom. 25ºC) | Entire Perimeter | 4 | 6 | 9 |
Note: The ambient test consisted of a single-acting, single-leaf proprietary doorset, fitted with the specified smoke seals, utilising the general principles of AS1530 Part 7 – 1998 (Method of measurement under ambient temperature conditions).
For more information and copies of relevant certificates contact Kilargo