Intumescent Fire Damper System Selector

Penetration System Building Element FRL Product Application / Mounting Detail Max. Size Condition
Wall WM1 Masonry / Concrete -/120/- IFD44C-LL Mounted in casing DD / DG 1200 x 1200
  WM1i Masonry / Concrete -/120/120 IFD44C-LL Mounted in casing DD with insulated rating 250 x 250 or 0.0625m2
  WM2 Masonry / Concrete -/240/- IFD44C-LL Mounted in casing DD / DG 300 x 300
  WM3i Masonry / Concrete -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 1200 x 1200
  WM4 Masonry / Concrete -/120/- IFD44C-LL Mounted hard up to slab with 30mm fire board packer - angles 3 sides only 300 x 300
  WM5 Masonry / Concrete -/120/120 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WM5i Masonry / Concrete -/120/120 IFDO-LL Transfer Air with mesh guard 350 DIA
  WM6 Masonry / Concrete -/120/- IFD44C-LL Mounted hard up to slab (with no packer) - angles 3 sides only 300 x 300
  WM6i Masonry / Concrete -/120/120 IFD44C-LL Mounted hard up to slab (with no packer) - angles 3 sides only 250 x 250 or 0.0625m2
  WD1i Dincel -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 600 x 600
  WD2 Dincel -/120/- IFD44C-LL Mounted in casing DD / DG 600 x 600
  WH1 Hebel -/120/- IFD44C-LL Mounted in casing DD / DG in 75SS system hebel wall 300 x 300 without build up
  WH1i Hebel -/120/120 IFD44C-LL Mounted in casing DD with insulation 75SS system hebel wall 250 x 250 or 0.0625m2
  WH2 Hebel -120/120 IFDO-LL DD / DG in 75SS system hebel wall 350 DIA
  WH2i Hebel -/120/120 IFD44C-LL Mounted in casing DD with insulation 75SS system hebel wall 250 x 250 or 0.0625m2
  WH3i Hebel -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh in 75SS hebel wall 300 x 300 without build up
  WH4 Hebel -120/120 IFDO-LL DD / DG in 75mm hebel wall with FR plasterboard liner on one side 350 DIA
  WH4i Hebel -120/120 IFDO-LL Transfer Air with mesh guard in 75mm hebel wall with FR plasterboard liner on one side 350 DIA
  WH5 Hebel -/120/- IFD44C-LL Mounted in casing DD / DG in 75mm hebel wall with plasterboard lining 300 x 300 without build up
  WH6i Hebel -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh in 75mm hebel wall with plasterboard lining 300 x 300 without build up
  WH7 Hebel -/120/- IFD44C-LL Mounted in casing tight to underside of slab with 30mm thick packer and angles on 3 sides of the IFD on 1 side of the wall 300 x 300
  WH7i Hebel -/120/120 IFD44C-LL Mounted in casing DD with insulation rating in 75mm hebel wall with FR plasterboard lining 250 x 250 or 0.0625m2
  WH8i Hebel -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh in 75SW hebel wall 300 x 300 without build up
  WH9 Hebel -120/120 IFDO-LL DD / DG in 75 hebel wall lined with plasterboard 350 DIA
  WH9i Hebel -/120/120 IFDO-LL Transfer Air with mesh guard in 75mm hebel wall lined with plasterboard 350 DIA
  WH10 Hebel -120/120 IFDO-LL DD / DG in 75 hebel wall 350 DIA
  WH10i Hebel -120/120 IFDO-LL Transfer Air with mesh guard in 75mm hebel wall 350 DIA
  WH11 Hebel -/120/- IFD44C-LL Mounted in casing DD / DG in 75SW system hebel wall 300 x 300 without build up
  WP1 FR Plasterboard 1 x 16 -/90/- IFD44C-LL Mounted in casing DD / DG 300 x 300 without build up
  WP1i FR Plasterboard 1 x 16 -/90/90 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 300 x 300 without build up
  WP2 FR Plasterboard 3 x 16 -/120/- IFD44C-LL Mounted in casing DD / DG 1200 x 1200
  WP2i FR Plasterboard 3 x 16 -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 1200 x 1200
  WP3 FR Plasterboard 2 x 16 -/120/120 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP3i FR Plasterboard 2 x 16 + 1 -/120/120 IFDO-LL Transfer Air with mesh guard 350 DIA
  WP4 FR Plasterboard 25 + 2 -/120/120 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP4i FR Plasterboard 3 x 16 + 1 -/120/120 IFDO-LL Transfer Air with mesh guard 350 DIA
  WP5 FR Plasterboard 3 x 16 + 1 -/120/120 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP5i FR Plasterboard 3 x 16 + 1 -/120/120 IFDO-LL Transfer Air with mesh guard 350 DIA
  WP6 FR Plasterboard 3 x 16 -/120/120 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP7 FR Plasterboard 2 x 16 -/120/- IFD44C-LL Mounted in casing DD / DG 1200 x 1200
  WP7i FR Plasterboard 2 x 16 -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 1200 x 1200
  WP8 FR Plasterboard 1 x 13 -/60/- IFD44C-LL Mounted in casing DD / DG 300 x 300 without build up
  WP8i FR Plasterboard 1 x 13 -/60/60 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 300 x 300 without build up
  WP9 FR Plasterboard 2 x 13 -/120/- IFD44C-LL Mounted in casing DD / DG 1200 x 1200
  WP9i FR Plasterboard 2 x 13 -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 1200 x 1200
  WP10 Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44C-LL Mounted in casing DD / DG 1200 x 1200
  WP12 FR Plasterboard 1 x 13 -/60/60 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP12i FR Plasterboard 1 x 13 -/60/60 IFDO-LL Transfer Air with mesh guard 350 DIA
  WP13 FR Plasterboard 1 x 16 -/90/90 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP13i FR Plasterboard 1 x 16 -/90/90 IFDO-LL Transfer Air with mesh guard 350 DIA
  WP14 FR Plasterboard 2 x 13 -/120/120 IFDO-LL Duct to duct / Duct to grille 350 DIA
  WP14i FR Plasterboard 2 x 13 -/120/120 IFDO-LL Transfer Air with mesh guard 350 DIA
  WP15i FR Plasterboard 1 x 16 + 1 -/90/90 IFD44C-LL Mounted in casing DD with insulation rating 250 x 250 or 0.0625m2
  WP16i FR Plasterboard 2 x 16 + 1 -/120/120 IFD44C-LL Mounted in casing DD with insulation rating 250 x 250 or 0.0625m2
  WP17i FR Plasterboard 1 x 13 + 1 -/60/60 IFD44C-LL Mounted in casing DD with insulation rating 250 x 250 or 0.0625m2
  WP18i FR Plasterboard 2 x 13 + 1 -/120/120 IFD44C-LL Mounted in casing DD with insulation rating 250 x 250 or 0.0625m2
  WRF1 Masonry -/120/- IFD44-LL Retrofit cell only in ductwork 600 x 600
  WRF2 Hebel -/120/- IFD44-LL Retrofit cell only in ductwork 300 x 300 without build up
  WRF3 Plasterboard 3 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork 600 x 600
  WRF4 Plasterboard 2 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork 600 x 600
  WRF5 Plasterboard 2 x 13 -/120/- IFD44-LL Retrofit cell only in ductwork 600 x 600
  WRF6 Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44-LL Retrofit cell only in ductwork 600 x 600
  WRF7 Plasterboard 1 x 16 -/90/- IFD44-LL Retrofit cell only in ductwork 300 x 300 without build up
  WRF8 Plasterboard 1 x 13 -/60/- IFD44-LL Retrofit cell only in ductwork 300 x 300 without build up
  WRF9 Dincel -/120/- IFD44-LL Retrofit cell only in ductwork 600 x 600
  WRF1s Masonry -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF2s Hebel -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF3s Plasterboard 3 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF4s Plasterboard 2 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF5s Plasterboard 2 x 13 -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF6s Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF7s Plasterboard 1 x 16 -/90/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF8s Plasterboard 1 x 13 -/60/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WRF9s Dincel -/120/- IFD44-LL Retrofit cell only in ductwork hard to slab 300 x 300
  WFB1 Fire Rated Board -/120/- IFD44C-LL Mounted in casing DD / DG 300 x 300
  WFB1i Fire Rated Board -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 300 x 300
  WFB3 Fire Rated Board + 2 x PB -/120/- IFD44C-LL Mounted in casing DD / DG 300 x 300
  WFB3i Fire Rated Board + 2 x PB -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 300 x 300
Shaftwall WSRF1 Masonry -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF2 Hebel -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF3 Plasterboard 3 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF4 Plasterboard 2 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF5 Plasterboard 2 x 13 -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF6 Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF7 Plasterboard 1 x 16 -/90/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF8 Plasterboard 1 x 13 -/60/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF9 Dincel -/120/- IFD44-LL Retrofit cell only in ductwork riser branch 600 x 600
  WSRF1s Masonry -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF2s Hebel -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF3s Plasterboard 3 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF4s Plasterboard 2 x 16 -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF5s Plasterboard 2 x 13 -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF6s Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF7s Plasterboard 1 x 16 -/90/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF8s Plasterboard 1 x 13 -/60/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSRF9s Dincel -/120/- IFD44-LL Retrofit cell only in ductwork riser branch hard to slab 300 x 300
  WSW1 Masonry -/120/- IFD44C-LL Mounted in casing - angle free riser connection 600 x 600 or 0.36 m2
  WSW2 Masonry -/120/- IFD44C-LL Mounted in casing - angle free riser connection tight to slab with packer 300 x 300
  WSW3 Masonry -/120/- IFD44C-LL Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic 300 x 300
  WSW4 Plasterboard 3 x 16 -/120/- IFD44C-LL Mounted in casing - angle free riser connection tight to slab with packer 300 x 300
  WSW5 Plasterboard 3 x 16 -/120/- IFD44C-LL Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic 300 x 300
  WSW6 Hebel -/120/- IFD44C-LL Mounted in casing - angle free riser connection 300 x 300 without build up
  WSW7 Hebel -/120/- IFD44C-LL Mounted in casing - angle free riser connection tight to slab with packer 300 x 300
  WSW8 Hebel -/120/- IFD44C-LL Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic 300 x 300
  WSW9 Plasterboard 3 x 16 -/120/- IFD44C-LL Mounted in casing - angle free riser connection 600 x 600 or 0.36 m2
  WSW10 Plasterboard 2 x 16 -/120/- IFD44C-LL Mounted in casing - angle free riser connection 600 x 600 or 0.36 m2
  WSW11 Plasterboard 1 x 13 -/60/- IFD44C-LL Mounted in casing - angle free riser connection 300 x 300 without build up
  WSW12 Plasterboard 2 x 13 -/120/- IFD44C-LL Mounted in casing - angle free riser connection 600 x 600 or 0.36 m2
  WSW13 Plasterboard 1 x 16 -/90/- IFD44C-LL Mounted in casing - angle free riser connection 300 x 300 without build up
  WSW14 Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44C-LL Mounted in casing - angle free riser connection 600 x 600 or 0.36 m2
  WSW15 Dincel -/120/- IFD44C-LL Mounted in casing - angle free riser connection 600 x 600
  WSW23 Masonry -/120/- IFD44-LL Cell only installed in riser with grille on one side 600 x 600 or 0.36 m2
  WSW24 Hebel -/120/- IFD44-LL Cell only installed in riser with grille on one side 300 x 300 without build up
  WSW25 Dincel -/120/- IFD44-LL Cell only installed in riser with grille on one side 600 x 600
  WSW27 Plasterboard 1 x 16 -/90/- IFD44-LL Cell only installed in riser with grille on one side 300 x 300 without build up
  WSW28 Plasterboard 2 x 16 -/120/- IFD44-LL Cell only installed in riser with grille on one side 600 x 600 or 0.36 m2
  WSW29 Plasterboard 3 x 16 -/120/- IFD44-LL Cell only installed in riser with grille on one side 600 x 600 or 0.36 m2
  WSW30 Plasterboard 1 x 13 -/60/- IFD44-LL Cell only installed in riser with grille on one side 300 x 300 without build up
  WSW31 Plasterboard 2 x 13 -/120/- IFD44-LL Cell only installed in riser with grille on one side 600 x 600 or 0.36 m2
  WSW32 Plasterboard 1 x 25 liner + 2 x 13 or 16 layers -/120/- IFD44-LL Cell only installed in riser with grille on one side 600 x 600 or 0.36 m2
Floor Slab FL1i Concrete Slab -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 1200 x 1200
  FL2 Concrete Slab -/120/- IFD44-LL Mounted in casing DD / DG 1200 x 1200
  FL3i Concrete slab -/120/120 IFD44-LL Mounted in casing DD with insulation rating 250 x 250 or 0.0625m2
  FL4 Concrete slab -/120/120 IFDO-LL Steel sleeve in penetration 350 DIA
  FFB1 Retrofit Fire board systems -/120/- IFD44-LL Mounted in casing DD / DG 300 x 300
  FFB2i Retrofit Fire board systems -/120/120 IFD44-LL Cell only - Air Transfer with grilles or flat vermin proof mesh 300 x 300
Ceiling CE1-60 13 & 16mm layer FR P/Board -/60/60 IFD-CE1-LL P/Board clad plenum box (60min RISF Incipient rated) 600 x 600
  CE1-90 2 x 16mm FR P/Board -/90/90 IFD-CE1-LL P/Board clad plenum box (up to 90min RISF Incipient rated) 600 x 600
  CE1-120 3 x 16mm FR P/Board -/120/120 IFD-CE1-LL P/Board clad plenum box (up to 120min RISF Incipient rated) 600 x 600
  CE4-60 13 & 16mm layer FR P/Board -/60/60 IFD-CE4-LL P/Board clad plenum box (60min RISF Incipient rated) 405 x 405
  CE4-90 2 x 16mm layer FR P/Board -/90/90 IFD-CE4-LL P/Board clad plenum box (up to 90min RISF Incipient rated) 405 x 405
  CE4-120 3 x 16mm layer FR P/Board -/120/120 IFD-CE4-LL P/Board clad plenum box (up to 120min RISF Incipient rated) 405 x 405
Door FD3 IFD-D in E-Core fire doors -/120/30 IFD-D Fitted to 37mm Mini & 47mm Maxi fire doors