Wall |
WM1
|
Masonry / Concrete |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WM1i
|
Masonry / Concrete |
-/120/120 |
IFD44C-LL |
Mounted in casing DD with insulated rating |
250 x 250 or 0.0625m2 |
|
|
WM2
|
Masonry / Concrete |
-/240/- |
IFD44C-LL |
Mounted in casing DD / DG |
300 x 300 |
|
|
WM3i
|
Masonry / Concrete |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WM4
|
Masonry / Concrete |
-/120/- |
IFD44C-LL |
Mounted hard up to slab with 30mm fire board packer - angles 3 sides only |
300 x 300 |
|
|
WM5
|
Masonry / Concrete |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WM5i
|
Masonry / Concrete |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WM6
|
Masonry / Concrete |
-/120/- |
IFD44C-LL |
Mounted hard up to slab (with no packer) - angles 3 sides only |
300 x 300 |
|
|
WM6i
|
Masonry / Concrete |
-/120/120 |
IFD44C-LL |
Mounted hard up to slab (with no packer) - angles 3 sides only |
250 x 250 or 0.0625m2 |
|
|
WD1i
|
Dincel |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
600 x 600 |
|
|
WD2
|
Dincel |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
600 x 600 |
|
|
WH1
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG in 75SS system hebel wall |
300 x 300 |
without build up |
|
WH1i
|
Hebel |
-/120/120 |
IFD44C-LL |
Mounted in casing DD with insulation 75SS system hebel wall |
250 x 250 or 0.0625m2 |
|
|
WH2
|
Hebel |
-120/120 |
IFDO-LL |
DD / DG in 75SS system hebel wall |
350 DIA |
|
|
WH2i
|
Hebel |
-/120/120 |
IFD44C-LL |
Mounted in casing DD with insulation 75SS system hebel wall |
250 x 250 or 0.0625m2 |
|
|
WH3i
|
Hebel |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh in 75SS hebel wall |
300 x 300 |
without build up |
|
WH4
|
Hebel |
-120/120 |
IFDO-LL |
DD / DG in 75mm hebel wall with FR plasterboard liner on one side |
350 DIA |
|
|
WH4i
|
Hebel |
-120/120 |
IFDO-LL |
Transfer Air with mesh guard in 75mm hebel wall with FR plasterboard liner on one side |
350 DIA |
|
|
WH5
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG in 75mm hebel wall with plasterboard lining |
300 x 300 |
without build up |
|
WH6i
|
Hebel |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh in 75mm hebel wall with plasterboard lining |
300 x 300 |
without build up |
|
WH7
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing tight to underside of slab with 30mm thick packer and angles on 3 sides of the IFD on 1 side of the wall |
300 x 300 |
|
|
WH7i
|
Hebel |
-/120/120 |
IFD44C-LL |
Mounted in casing DD with insulation rating in 75mm hebel wall with FR plasterboard lining |
250 x 250 or 0.0625m2 |
|
|
WH8i
|
Hebel |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh in 75SW hebel wall |
300 x 300 |
without build up |
|
WH9
|
Hebel |
-120/120 |
IFDO-LL |
DD / DG in 75 hebel wall lined with plasterboard |
350 DIA |
|
|
WH9i
|
Hebel |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard in 75mm hebel wall lined with plasterboard |
350 DIA |
|
|
WH10
|
Hebel |
-120/120 |
IFDO-LL |
DD / DG in 75 hebel wall |
350 DIA |
|
|
WH10i
|
Hebel |
-120/120 |
IFDO-LL |
Transfer Air with mesh guard in 75mm hebel wall |
350 DIA |
|
|
WH11
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG in 75SW system hebel wall |
300 x 300 |
without build up |
|
WP1
|
FR Plasterboard 1 x 16 |
-/90/- |
IFD44C-LL |
Mounted in casing DD / DG |
300 x 300 |
without build up |
|
WP1i
|
FR Plasterboard 1 x 16 |
-/90/90 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
without build up |
|
WP2
|
FR Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP2i
|
FR Plasterboard 3 x 16 |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WP3
|
FR Plasterboard 2 x 16 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP3i
|
FR Plasterboard 2 x 16 + 1 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP4
|
FR Plasterboard 25 + 2 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP4i
|
FR Plasterboard 3 x 16 + 1 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP5
|
FR Plasterboard 3 x 16 + 1 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP5i
|
FR Plasterboard 3 x 16 + 1 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP6
|
FR Plasterboard 3 x 16 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP7
|
FR Plasterboard 2 x 16 |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP7i
|
FR Plasterboard 2 x 16 |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WP8
|
FR Plasterboard 1 x 13 |
-/60/- |
IFD44C-LL |
Mounted in casing DD / DG |
300 x 300 |
without build up |
|
WP8i
|
FR Plasterboard 1 x 13 |
-/60/60 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
without build up |
|
WP9
|
FR Plasterboard 2 x 13 |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP9i
|
FR Plasterboard 2 x 13 |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WP10
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP12
|
FR Plasterboard 1 x 13 |
-/60/60 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP12i
|
FR Plasterboard 1 x 13 |
-/60/60 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP13
|
FR Plasterboard 1 x 16 |
-/90/90 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP13i
|
FR Plasterboard 1 x 16 |
-/90/90 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP14
|
FR Plasterboard 2 x 13 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP14i
|
FR Plasterboard 2 x 13 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP15i
|
FR Plasterboard 1 x 16 + 1 |
-/90/90 |
IFD44C-LL |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WP16i
|
FR Plasterboard 2 x 16 + 1 |
-/120/120 |
IFD44C-LL |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WP17i
|
FR Plasterboard 1 x 13 + 1 |
-/60/60 |
IFD44C-LL |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WP18i
|
FR Plasterboard 2 x 13 + 1 |
-/120/120 |
IFD44C-LL |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WRF1
|
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF2
|
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
300 x 300 |
without build up |
|
WRF3
|
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF4
|
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF5
|
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF6
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF7
|
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork |
300 x 300 |
without build up |
|
WRF8
|
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork |
300 x 300 |
without build up |
|
WRF9
|
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF1s
|
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF2s
|
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF3s
|
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF4s
|
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF5s
|
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF6s
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF7s
|
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF8s
|
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF9s
|
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WFB1
|
Fire Rated Board |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
300 x 300 |
|
|
WFB1i
|
Fire Rated Board |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
|
|
WFB3
|
Fire Rated Board + 2 x PB |
-/120/- |
IFD44C-LL |
Mounted in casing DD / DG |
300 x 300 |
|
|
WFB3i
|
Fire Rated Board + 2 x PB |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
|
Shaftwall |
WSRF1
|
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF2
|
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF3
|
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF4
|
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF5
|
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF6
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF7
|
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF8
|
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF9
|
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF1s
|
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF2s
|
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF3s
|
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF4s
|
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF5s
|
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF6s
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF7s
|
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF8s
|
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF9s
|
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSW1
|
Masonry |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW2
|
Masonry |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection tight to slab with packer |
300 x 300 |
|
|
WSW3
|
Masonry |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic |
300 x 300 |
|
|
WSW4
|
Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection tight to slab with packer |
300 x 300 |
|
|
WSW5
|
Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic |
300 x 300 |
|
|
WSW6
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
300 x 300 |
without build up |
|
WSW7
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection tight to slab with packer |
300 x 300 |
|
|
WSW8
|
Hebel |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection tight to slab with IBS rod & mastic |
300 x 300 |
|
|
WSW9
|
Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW10
|
Plasterboard 2 x 16 |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW11
|
Plasterboard 1 x 13 |
-/60/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
300 x 300 |
without build up |
|
WSW12
|
Plasterboard 2 x 13 |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW13
|
Plasterboard 1 x 16 |
-/90/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
300 x 300 |
without build up |
|
WSW14
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW15
|
Dincel |
-/120/- |
IFD44C-LL |
Mounted in casing - angle free riser connection |
600 x 600 |
|
|
WSW23
|
Masonry |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW24
|
Hebel |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
300 x 300 |
without build up |
|
WSW25
|
Dincel |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 |
|
|
WSW27
|
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
300 x 300 |
without build up |
|
WSW28
|
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW29
|
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW30
|
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
300 x 300 |
without build up |
|
WSW31
|
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW32
|
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
Floor Slab |
FL1i
|
Concrete Slab |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
FL2
|
Concrete Slab |
-/120/- |
IFD44-LL |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
FL3i
|
Concrete slab |
-/120/120 |
IFD44-LL |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
FL4
|
Concrete slab |
-/120/120 |
IFDO-LL |
Steel sleeve in penetration |
350 DIA |
|
|
FFB1
|
Retrofit Fire board systems |
-/120/- |
IFD44-LL |
Mounted in casing DD / DG |
300 x 300 |
|
|
FFB2i
|
Retrofit Fire board systems |
-/120/120 |
IFD44-LL |
Cell only - Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
|
Ceiling |
CE1-60
|
13 & 16mm layer FR P/Board |
-/60/60 |
IFD-CE1-LL |
P/Board clad plenum box (60min RISF Incipient rated) |
600 x 600 |
|
|
CE1-90
|
2 x 16mm FR P/Board |
-/90/90 |
IFD-CE1-LL |
P/Board clad plenum box (up to 90min RISF Incipient rated) |
600 x 600 |
|
|
CE1-120
|
3 x 16mm FR P/Board |
-/120/120 |
IFD-CE1-LL |
P/Board clad plenum box (up to 120min RISF Incipient rated) |
600 x 600 |
|
|
CE4-60
|
13 & 16mm layer FR P/Board |
-/60/60 |
IFD-CE4-LL |
P/Board clad plenum box (60min RISF Incipient rated) |
405 x 405 |
|
|
CE4-90
|
2 x 16mm layer FR P/Board |
-/90/90 |
IFD-CE4-LL |
P/Board clad plenum box (up to 90min RISF Incipient rated) |
405 x 405 |
|
|
CE4-120
|
3 x 16mm layer FR P/Board |
-/120/120 |
IFD-CE4-LL |
P/Board clad plenum box (up to 120min RISF Incipient rated) |
405 x 405 |
|
Door |
FD3 |
IFD-D in E-Core fire doors |
-/120/30 |
IFD-D |
Fitted to 37mm Mini & 47mm Maxi fire doors |
|
|